APC GUTOR PXC IEC 30kVA, 3:1 400/230V, IP42, No Transformer, unitary or parallel redundant on option – GUPXC30I2

  • APC GUTOR PXC IEC 30kVA
  • Main Input Voltage : 400 V 3 phases
  • Main Output Voltage : 230 V
  • Wave type : Sine wave
  • Bypass type : Built-in bypass
  • Battery type : External battery system
  • Part No : GUPXC30I2

 

For The Immediate delivery contact the sales team. Usually, Ship in 2-3 days, back order ship in 4-12 Weeks, images are for illustration purposes only.

AED 46,851.00 excl. VAT

Best Price: AED 45,679.73 on Bank Transfer / Cash Payment (-AED 1,171.28)

Available on backorder

Estimated delivery between Mar 4, 2025 - Apr 9, 2025
7 + 1 =
SKU: GUPXC30I2 Categories: , Tags: ,

APC GUTOR PXC IEC 30kVA, 3:1 400/230V, IP42, No Transformer, unitary or parallel redundant on option – GUPXC30I2

 

  • Main Input Voltage : 400 V 3 phases
  • Main Output Voltage : 230 V
  • Wave type : Sine wave
  • Bypass type : Built-in bypass
  • Battery type : External battery system
  • Warranty : 1-Year

 

PN : GUPXC30I2

 

APC GUPXC50H2 Image


 

Overview

 

High performance, compact 3 phase UPS power protection fully standardized for heavy industrial applications and harsh environments. Available in 3:3 and 3:1 configurations.

APC Schneider Electric Image

APC Schneider Electric Image

 

Published on lastbestprice.com

 

Detailed Tech Specification

 

Main

Main Input Voltage 400 V 3 phases
Other Input Voltage 400 V
Main Output Voltage 230 V
Other Output Voltage 230 V
Rated power in W 24000 W
Rated power in VA 30000 VA
Battery type External battery system
provided equipment Dust filter
Installation guide
Network management card
User manual

 

General

Bypass voltage tolerance +/- 10 %
Max bypass input current 145 A
Bypass current protection 200 A
Number of power module free slots 0
Number of power module filled slots 0
Redundant No

 

Physical

colour Light grey
Height 210 cm
Width 60 cm
Depth 80 cm
Net weight 340 kg
Mounting preference No preference
Mounting mode Not rack-mountable
Two post mountable 0
USB compatible No

 

Input

network frequency 45…65 Hz
number of input connectors 1 hard wire 5-wire (3P + N + E)
Maximum input current 62 A
Switching current capacity 80 A
Max short time withstand current 65 kA
Input harmonic distortion Less than 5 % for full load
Input protection type Upstream protection according to source
input current 62 A per phase (3 phases)
Load power factor 0.5 leading to 0.5 lagging without derating
Input Power Factor at Full Load 0.97

 

Output

Maximum configurable power in W 24000 W
Harmonic distortion Less than 5 %
output frequency 50/60 Hz +/- 1 Hz sync to mains
60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
Crest factor Unlimited
UPS type Double conversion online
Wave type Sine wave
Output voltage tolerance +/- 1 %
Output harmonic distortion < 2% at 100% linear load and < 5% at 100% non-linear load
Output overload operation 10 minutes at 125% and 60 seconds at 150%
Required output current protection 200 A
Neutral output current 130 A
Bypass type Built-in bypass
efficiency 94.3 % (full load)
94.6 % (half load)
93.8 % (in battery operation)
Maximum configurable power in VA 30000 VA

 

Conformance

Product certifications CE
Marking CE Mark
standards IBC 2012
IEC 62040-1-1
IEC 62040-2
IEC 62040-3
ISTA 2B
VFI-SS-111

 

Environmental

Ambient air temperature for operation -10…40 °C
relative humidity 0…95 % non-condensing
Operating altitude 0…10000 ft
Ambient air temperature for storage -30…70 °C
storage Relative Humidity 0…95 % Non-condensing
Storage altitude 0.00…4572.00 m
Acoustic level 65 dBA
Heat dissipation 4959 Btu/h
IP degree of protection IP42 with air filter

 

Batteries & Runtime

Number of battery filled slots 0
Number of battery free slots 0
Max current discharge 77.9 A
Battery power in VAH 0 VAh runtime
Extended runtime 0

 

Communications & Management

Free slots 1
Preinstalled device Network management card 2 with environmental monitoring, out of band access and Modbus
control panel Multifunction LCD status and control console
alarm Audible and visible alarms : prioritized by severity
Emergency power off Yes

 

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 230.0 cm
Package 1 Width 82.0 cm
Package 1 Length 108.2 cm
Package 1 Weight 386.739 kg

 

Contractual warranty

Warranty 1 year on-site repair or replace with factory authorized Start-Up

 