Shop Exclusive
APC Symmetra PX 48kW All-In-One 400V – SY48K48H-PD
[ratingwidget type="page"]
For The Immediate delivery contact the sales team. Usually, Ship in 2-3 days, back order ship in 4-12 Weeks, images are for illustration purposes only.
AED 193,222.00 excl. VAT
Best Price: AED 188,391.45 on Bank Transfer / Cash Payment (-AED 4,830.55)
Estimated delivery between Dec 26, 2024 - Jan 11, 2025
APC Symmetra PX 48kW All-In-One 400V – SY48K48H-PD
Overview
SY48K48H-PD Features
Run time for load
4m 39s
Max. Capacity Used
Output power capacity
48.0kWatts / 48.0kVA
Rack Height
42U
Nominal Output Voltage
230V, 400V 3PH
Nominal Input Voltage
400V 3PH
Input Connections
Hard wire 5-wire (3P + N + E)
Maximum Input Current
98.0A
Symmetra PX All-In-One 48kW Scalable to 48kW, 400V
Scalable power, runtime & distribution in a high-density, single-frame design. This high-efficiency 3-phase UPS scales as your data center grows up to 48kW/48kVA. Suitable for small & medium data center applications.
Includes: Network management card, Start-up service
- Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
- Battery modules connected in parallel
Delivers higher availability through redundant batteries.
- Battery replacement without tools
Enables fast battery replacement, lowering Mean Time to Repair (MTTR).
- Dual mains input
Increases availability by allowing the UPS to be connected to two separate power sources.
- Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
- Manageable external batteries
Reduces preventative maintenance service needs by monitoring the health and status of the external batteries and their expected runtime.
- Swappable batteries
Allows quick addition of runtime capacity or replacement of existing battery modules. Installed modules are automatically recognized by the system.
- Temperature-compensated battery charging
Prolongs battery life by regulating the charge voltage according to battery temperature.
Symmetra PX Features & Benefits
Agility
Scalable power capacity
Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
Intelligent Card Slot
Customize UPS capabilities with management cards.
Programmable frequency
Ensures compatibility with different input frequencies.
Availability
Swappable power modules
Allows quick addition of power capacity or replacement of existing power modules. Installed modules are automatically recognized by the system.
Power Modules connected in parallel
Enhances availability by allowing immediate, seamless recovery from isolated module failures.
Redundant Intelligence Modules
Provides higher availability to the UPS connected loads by giving redundant communication paths to critical UPS functions.
Modular design
Provides scalability, N+1 redundancy, fast serviceability, and reduced maintenance requirements via self-diagnosing, swappable, and field-replaceable modules.
Network manageable
Most models provide remote power management options of the UPS over the network. Many do not have NMC embedded.
Battery modules connected in parallel
Delivers higher availability through redundant batteries.
Configurable for N+1 internal redundancy
Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS power overload or fault.
User-replaceable batteries
Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
User-replaceable power modules
Enables simple upgrades and replacements of the Power Modules.
Published on lastbestprice.com
Manageability
Audible alarms
Provides notification of changing utility power and UPS power conditions
Integrates with StruxureWare Data Center Expert
An IT-ready, scalable access monitoring system that collects, organizes, and distributes critical alerts, surveillance video and key information, providing a unified view of complex physical infrastructure environments from anywhere on the network
LED status indicators
Quickly understand unit and power status with visual indicators.
Sustainability
EU CoC for UPS
Ensures that UPSs sold in the EU are highly efficient
Total cost of Ownership
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
5×8 Start-up service included
Required for full coverage of factory warranty
Fully-rated power kVA equals kW
Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
Output
Max Configurable Power (Watts)
48.0kWatts / 48.0kVA
Output Voltage Note
Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Output Voltage Distortion
Less than 2 %
Output Frequency (sync to mains)
50 Hz +/- 0.1 % For 50 Hz nominal Unsynchronised, 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz Sync to mains, 60 Hz +/- 0.1 % For 60 Hz nominal Unsynchronised
Other Output Voltages
380 V, 400 V, 415 V
Topology
Double conversion online
Waveform type
Sine wave
Overload Operation
10 minutes at 125% and 60 seconds at 150%
Output Voltage THD
< 2% for 0 to 100% linear load and < 6% for full non-linear load
Output Voltage Tolerance
+/- 1% static and +/- 5% at 100% load step
Bypass
Built-in static bypass
Input
Input frequency
40 – 70 Hz
Input voltage range for main operations
340 – 477V
Input Total Harmonic Distortion
Less than 5 % for full load
Type of Input Protection Required
GL fuse
Other Input Voltages
380 V, 400 V, 415 V
Maximum Short Circuit Withstand (Icw)
30.0kAmps
Input Power Factor at Full Load
0.99
Batteries & Runtime
Battery type
VRLA
Included Battery Modules
4
Typical recharge time
3hour(s)
Nominal Battery Voltage
+/- 192 V (split battery referenced to neutral)
End of Discharge Maximum Battery Current
165.0A
RBC Quantity
4
Battery Charge Power (Watts)
4.593kWatts
DC Overcurrent Protection
1008A
Extendable Run Time
1
End of Discharge Battery Voltage
+/- 154 V
Efficiency in Battery Operation
94.0 %
Maximum Available Short Circuit Current
4kAmps
Overload Operation
10 minutes at 125% and 60 seconds at 150%
Runtime
Efficiency
Communications & Management
Interface Port(s)
DB-9 RS-232, SmartSlot
Control panel
Multifunction LCD status and control console
Audible Alarm
Alarm when on battery : distinctive low battery alarm : configurable delays
Emergency Power Off (EPO)
Yes
Available SmartSlot™ Interface Quantity
2
Physical
Maximum Height
1991MM, 199.1CM
Maximum Width
600MM, 60.0CM
Maximum Depth
1070MM, 107.0CM
Net Weight
796.0KG
Shipping weight
858.0KG
Shipping Height
2140MM, 214.0CM
Shipping Width
848MM, 84.8CM
Shipping Depth
1210MM, 121.0CM
Color
Black
Published on lastbestprice.com
Environmental
Operating Temperature
0 – 40 °C
Operating Relative Humidity
0 – 95 %
Operating Elevation
0 – 1015.9meters
Storage Temperature
-15 – 40 °C
Storage Relative Humidity
0 – 95 %
Storage Elevation
0 – 15240meters
Audible noise at 1 meter from surface of unit
61.0dBA
Online thermal dissipation
7719.0BTU/hr
Protection Class
NEMA 1
Conformance
Approvals
EN 50091-1, EN/IEC 62040-1-1, EN/IEC 62040-2, EN/IEC 62040-3, EUROBAT, ISO 14001, ISO 9001, VFI-SS-111
Standard warranty
1 year on-site repair or replace with factory authorized Start-Up
Sustainable Offer Status
RoHS
Compliant
General
Bypass Connection
5 wire (3P + N + E)
Bypass Protection Device
80.0
Max Bypass Input Current
80.0A
Reviews
There are no reviews yet.