GVSUPS20K0B4HS Features

Run time for load

Max. Capacity Used

100%

Output power capacity

20.0kWatts / 20.0kVA

Nominal Output Voltage

400V 3PH

Nominal Input Voltage

400V 3PH

Maximum Input Current

36.0A
Galaxy VS UPS 20kW 400V for up to 4 internal 9Ah smart modular battery strings, Start-up 5x8

Galaxy VS UPS 20kW 400V for up to 4 internal 9Ah smart modular battery strings, Start-up 5×8

Highly efficient, easy-to-deploy 20kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. This UPS is for up to 4 smart modular high capacity battery strings, but is supplied without batteries, so you can easily customize the battery runtime. Includes 5×8 start-up service.
Includes: Dust filter, EcoStruxure Ready, Installation manual, Integrated network management, Start-up service

Galaxy VS UPS 20kW 400V for up to 4 internal 9Ah smart modular battery strings, Start-up 5x8

Galaxy VS Features & Benefits

Total cost of Ownership

Robust operation

No power derating in kW up to 40°C or 104°F.

Wide input voltage range

Designed for harsh electrical environments to save battery life.

High efficiency in double conversion mode

Consistently high power quality at high efficiency, even at low load levels. Any disturbances on the distribution waveform are regenerated via the zero transfer time AC to DC then DC to AC conversion process. The battery is only used as a back-up source.

Input power factor correction

Minimizes installation costs by enabling the use of smaller generators and cabling.

Compatible with Galaxy Lithium-ion Battery Cabinets

Reduces system footprint and weight, cooling and maintenance requirements, and total cost of ownership; offers double the life of VRLA batteries; and improves backup storage predictability and manageability. Galaxy VS UPSs for external batteries are compatible with Galaxy Lithium-ion Battery Cabinets.

ECOnversion mode

Operating mode that ensures ultra high efficiency while charging the batteries, conditioning the load power factor and ensuring a Class 1 output voltage regulation.

Compact UPS

High-density technology and full front access make this UPS a footprint saver well suited for confined spaces.

Serviceability

Modular UPS design

Provides design redundancy and fast serviceability with improved mean time to repair, via self-diagnosing, field-replaceable modules.

Multiple levels of service offers

With the option of packages or individual service components, our services are structured to allow you to pick and choose what you would like Schneider Electric to do for you.

EcoStruxure IT Expert

From your smartphone or computer, connect to our cloud-based, do-it-yourself monitoring system that collects, organizes, and distributes critical alerts and key information in real time, providing a unified view of even highly distributed physical infrastructure environments. Optimize your uptime and maintenance planning, and anticipate infrastructure issues before they occur with advanced analytics and performance benchmarking. Available in select countries. To learn more, visit a target=”_blank” href=”http://www.ecostruxureit.com”ecostruxureit.com/a.

Front-access servicing

Simplifies installation and UPS maintenance while minimizing space requirements.

Availability

Embedded Network Management Card

Allows you to remotely manage alert thresholds and monitor your UPS over EcoStruxure IT, Web, SNMP, or Modbus TCP and Modbus RTU.

Flexible DC bus

Optimizes battery sizing and supports a wide range of energy storage technologies, including VRLA, Li-ion, and NiCd batteries.

Built-in backfeed protection

Full built-in backfeed contactor ensures that no electricity is sent back to the grid.

Parallel-capacity capability

Increases total power capacity by using multiple uninterruptible power supplies simultaneously.

Parallel-redundant capability

Powers the connected equipment with multiple uninterruptible power supplies and redundant fan design to increase system redundancy.
Galaxy VS UPS 20kW 400V for up to 4 internal 9Ah smart modular battery strings, Start-up 5x8

Detailed Tech Specification

Output

Max Configurable Power (Watts)

20.0kWatts / 20.0kVA

Output Voltage Distortion

Less than 3 %

Output Frequency (sync to mains)

50 Hz Sync to mains, 60 Hz Sync to mains

Other Output Voltages

380 V, 415 V

Load Crest Factor

2.5

Waveform type

Sine wave

Overload Operation

10 minutes at 125% and 60 seconds at 150%

Output Voltage THD

< 1% linear load and < 3% non-linear load

Output Voltage Tolerance

+/- 5% after 2ms, +/-1% after 50ms

Bypass

Built-in static bypass

Input

Input frequency

40 – 70 Hz

Input voltage range for main operations

340 – 460 (400 V)V

Input Total Harmonic Distortion

Less than 3 % for full load

Other Input Voltages

380 V, 415 V

Maximum Short Circuit Withstand (Icw)

65.0kAmps

Input Power Factor at Full Load

0.99

Batteries & Runtime

Battery type

Internal modular battery, VRLA

Nominal Battery Voltage

480 V

End of Discharge Maximum Battery Current

54.0A

End of Discharge Battery Voltage

384 V

Communications & Management

Control panel

Touch screen LCD user interface

Audible Alarm

Audible and visible alarms prioritized by severity

Physical

Maximum Height

1485MM, 148.5CM

Maximum Width

521MM, 52.1CM

Maximum Depth

847MM, 84.7CM

Net Weight

200.0KG

Shipping weight

200.0KG

Shipping Height

1680MM, 168.0CM

Shipping Width

640MM, 64.0CM

Shipping Depth

990MM, 99.0CM

Color

White

Environmental

Operating Temperature

0 – 40 °C

Operating Relative Humidity

0 – 95 (Non-condensing) %

Operating Elevation

0 – 1005.84meters

Storage Temperature

-15 – 40 °C

Storage Relative Humidity

10 – 80 (Non-condensing) %

Storage Elevation

0 – 3048meters

Audible noise at 1 meter from surface of unit

55.0dBA

Online thermal dissipation

2431.0BTU/hr

Protection Class

IP20

Conformance

Approvals

IEC 62040-1-1, IEC 62040-2, OSHPD

Standard warranty

1 year on-site repair or replace with factory authorized Start-Up

Sustainable Offer Status

RoHS

Compliant

Other Environmental Compliance

China RoHS