Galaxy VS UPS 50kW 400V for External Batteries Start-up 5×8 – GVSUPS50KHS

RoHS

 

 

Galaxy VS UPS 50kW 400V for External Batteries, Start-up 5x8

 

 

Overview

 

GVSUPS50KHS Features

Max. Capacity Used

100%

Output power capacity

50.0kWatts / 50.0kVA

Output Connections

(1) Hard wire 5-wire (3P + N + E) (Battery Backup)

Nominal Output Voltage

400V 3PH

Nominal Input Voltage

400V 3PH

Input Connections

Hard wire 4-wire (3P + E), Hard wire 5-wire (3P + N + E)

Maximum Input Current

91.0A
Galaxy VS UPS 50kW 400V for External Batteries, Start-up 5x8

Galaxy VS UPS 50kW 400V for External Batteries, Start-up 5×8

Highly efficient, easy-to-deploy 50kW, 400V 3-phase uninterruptible power supply (UPS) that brings best-in-class power protection to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Compact design, high-density technology and modular architecture keep total cost of ownership low and operational efficiency at the highest levels. Galaxy VS reduces your energy losses by up to 66% with the patented ECOnversion mode – reaching up to 99% efficiency levels and delivering more energy savings than even our industry-leading 97% efficiency in normal operating mode. The UPS is EcoStruxure-ready to give you peace of mind with cloud-based remote monitoring and management via your smartphone. Includes 5×8 start-up service. For battery runtime details, see the runtime charts published under the Documents tab.
Includes: Dust filter, Installation guide, Integrated network management, Power modules ship installed, Start-up service, Top and bottom cable entry
Galaxy VS UPS 50kW 400V for External Batteries, Start-up 5x8

Galaxy VS Features & Benefits

Availability

Embedded Network Management Card

Allows you to remotely manage alert thresholds and monitor your UPS over EcoStruxure IT, Web, SNMP, or Modbus TCP and Modbus RTU.

Parallel-redundant capability

Powers the connected equipment with multiple uninterruptible power supplies and redundant fan design to increase system redundancy.

Built-in backfeed protection

Full built-in backfeed contactor ensures that no electricity is sent back to the grid.

Parallel-capacity capability

Increases total power capacity by using multiple uninterruptible power supplies simultaneously.

Flexible DC bus

Optimizes battery sizing and supports a wide range of energy storage technologies, including VRLA, Li-ion, and NiCd batteries.

Serviceability

Multiple levels of service offers

With the option of packages or individual service components, our services are structured to allow you to pick and choose what you would like Schneider Electric to do for you.

Modular UPS design

Provides design redundancy and fast serviceability with improved mean time to repair, via self-diagnosing, field-replaceable modules.

Front-access servicing

Simplifies installation and UPS maintenance while minimizing space requirements.

EcoStruxure IT Expert

From your smartphone or computer, connect to our cloud-based, do-it-yourself monitoring system that collects, organizes, and distributes critical alerts and key information in real time, providing a unified view of even highly distributed physical infrastructure environments. Optimize your uptime and maintenance planning, and anticipate infrastructure issues before they occur with advanced analytics and performance benchmarking. Available in select countries. To learn more, visit a target=”_blank” href=”http://www.ecostruxureit.com”ecostruxureit.com/a.

Total cost of Ownership

High efficiency in double conversion mode

Consistently high power quality at high efficiency, even at low load levels. Any disturbances on the distribution waveform are regenerated via the zero transfer time AC to DC then DC to AC conversion process. The battery is only used as a back-up source.

Wide input voltage range

Designed for harsh electrical environments to save battery life.

Robust operation

No power derating in kW up to 40°C or 104°F.

Input power factor correction

Minimizes installation costs by enabling the use of smaller generators and cabling.

Compact UPS

High-density technology and full front access make this UPS a footprint saver well suited for confined spaces.

ECOnversion mode

Operating mode that ensures ultra high efficiency while charging the batteries, conditioning the load power factor and ensuring a Class 1 output voltage regulation.

Compatible with Galaxy Lithium-ion Battery Cabinets

Reduces system footprint and weight, cooling and maintenance requirements, and total cost of ownership; offers double the life of VRLA batteries; and improves backup storage predictability and manageability. Galaxy VS UPSs for external batteries are compatible with Galaxy Lithium-ion Battery Cabinets.
Galaxy VS UPS 50kW 400V for External Batteries, Start-up 5x8

Detailed Tech Specification

 

Output

Max Configurable Power (Watts)

50.0kWatts / 50.0kVA

Output Voltage Distortion

Less than 3 %

Output Frequency (sync to mains)

50 Hz +/- 0.1 % For 50 Hz nominal Unsynchronised, 50 Hz Sync to mains, 60 Hz +/- 0.1 % For 60 Hz nominal Unsynchronised, 60 Hz Sync to mains

Other Output Voltages

380 V, 415 V

Load Crest Factor

2.5

Waveform type

Sine wave

Overload Operation

10 minutes at 125% and 60 seconds at 150%

Output Voltage THD

< 1% linear load and < 3% non-linear load

Output Voltage Tolerance

+/-1% after 50ms

Bypass

Built-in static bypass

Input

Input frequency

40 – 70 Hz

Input voltage range for main operations

340 – 460 (400 V)V

Input Total Harmonic Distortion

Less than 3 % for full load

Other Input Voltages

380 V, 415 V

Maximum Short Circuit Withstand (Icw)

65.0kAmps

Input Power Factor at Full Load

0.99

Batteries & Runtime

Battery type

External battery system, Li-Ion (Lithium-Ion), VRLA

Nominal Battery Voltage

480…576 V DC

End of Discharge Maximum Battery Current

136.0A

End of Discharge Battery Voltage

384 V DC

Communications & Management

Interface Port(s)

GVS_Parallel, GVS_WideUPS_AirFilter, GVS_WideUPSMBC_SeismicKit

Control panel

Touch screen LCD user interface

Audible Alarm

Audible and visible alarms prioritized by severity

Available SmartSlot™ Interface Quantity

1

Physical

Maximum Height

1485MM, 148.5CM

Maximum Width

521MM, 52.1CM

Maximum Depth

847MM, 84.7CM

Net Weight

206.0KG

Shipping weight

235.0KG

Shipping Height

1680MM, 168.0CM

Shipping Width

640MM, 64.0CM

Shipping Depth

990MM, 99.0CM

Color

White

Environmental

Operating Temperature

0 – 40 °C

Operating Relative Humidity

0 – 95 (Non-condensing) %

Operating Elevation

0 – 1000.05meters

Storage Temperature

-25 – 55 °C

Storage Relative Humidity

10 – 80 (Non-condensing) %

Storage Elevation

0 – 15240meters

Audible noise at 1 meter from surface of unit

65.0dBA

Online thermal dissipation

4915.0BTU/hr

Protection Class

IP21

Conformance

Approvals

CSA C22.2 No 107.3, EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, FCC part 15 class A, IEC 60721-4-2 level 2M2, UL 1778 5th edition

Standard warranty

1 year on-site repair or replace with factory authorized Start-Up

Sustainable Offer Status

RoHS

Compliant

PEP

Available in Documentation tab

Other Environmental Compliance

China RoHS

General

Max Bypass Input Current

80.0A